Fabrication and Performance testing of Evaporative Air Cooler with Solar Liquid Desiccant Dehumidification
Mandar M. Lele, R. J. Yadav, , S. R. Kale,
Published in INPRESSCO
2017
Volume: 1.0
   
Issue: Special Issue - 7
Pages: 347.0 - 351.0
Abstract
The extensive effort has made to fabricate and analyze the evaporative cooler with liquid-desiccant regeneration process. A temperature drop of around 4 degrees and a humidity reduction of around 14-16 percent as compared to direct contact evaporative cooler achieved. The enhanced average cooling efficiency of the evaporative cooler is41.828 % achieved with Average dehumidification capacity obtained at different concentrations of desiccantare: At 20% concentration of desiccant = 4.3695 lph, At 30% concentration of desiccant = 5.4845 lph, At 40% concentration of desiccant = 6.391 lph
About the journal
JournalInternational Journal of Current Engineering and Technology
PublisherINPRESSCO
Open Access0